Model: greenBOX Pro, product EG.155 |
Certification: CE, CA UK (LVD - Low Voltage Directive, EMC - Electromagnetic Compatibility Directive); UL per request |
User Interface: you can connect external HDMI monitor or access greenBOX via LAN; built-in web server, user interface is accessible via any connected device with browser; remote access via internet; by using modern internet technologies Web User Interface response is immediate and fluent, scalable to different screen resolution. |
Software Updates: Software is automatically updatable via internet connection (Ethernet port) |
Size: Approx. 16.8” width x 9.8” height x 4.4” deep (425 mm x 250 mm x 110 mm), green painted metal type 1 enclosure intended for a wall installation. |
Weight: Approx 17 Lb (8 kg) |
Power Supply: IEC-60230 C14 power socket for C13 IEC cable, 120 – 240 V AC, 50-60 Hz, 120 W, peak 180W; power supply CE, UK CA, UL508A, UL listed, EMI input filter. |
Modbus Ports: Three Modbus over RS485 for Ecogate Smart gates, and for Ecogate Power MASTER Variable Frequency Drives; and for other Modbus devices (air velocity sensors, pressure transmitters, temperature sensors etc.), the 24V DC is provided for Ecogate gates and other Modbus devices, each 24V DC power output is electronically protected, limit is set to 3.3A, and adjustable up to 4A in user interface. |
Front Panel Touchscreen: N/A (it is possible to connect external HDMI monitor for setup) |
Ecogate Compatibility: Ecogate Smart gates 2” to 26” ( + metric 120, 140, 160mm), Ecogate VOLT or current sensors, Ecogate Power Master variable frequency drives for 10 to 400 HP fan motors, Ecogate Master and Sensor cables. |
Inputs: Four optically isolated digital inputs (24V DC provided by greenBOX, current 10mA); function selectable from the listbox in user interface. |
Outputs: Four free (dry) contacts, three Normally Open (NO), one Normally Open and Normally Closed (NO and NC); function selectable from the listbox in user interface. Maximal 24V DC or AC, 1A. Output for status LED lights: Error (Red), Warning (Orange), OK (Green), maximal total current 0.37A, 24V DC (8.8W). |
Other Terminals: Ethernet up to 1Gbps, USB for external keyboard/mouse. |
Settings: Metric or Imperial units selection, time zone selection, gate timings (on delay, off delay), gate diameters, design drop air velocity, minimum airflow to maintain transport air velocity as a percentage of total air volume in many duct zones, negative pressure compensation (for the workstations at the end of ducting), dust collector on delay (0-99 sec) and dust collector shut-off delay (0 to 99 minutes), variable frequency drive minimal and maximum RPM, security functions (configurable in setup: all gates can be open or closed in stop mode), CLEANING function (to sweep duct in regular intervals, or at system stop); Fan and filter Pressure monitoring with separate Warning and Error levels both for Minimum and Maximum pressure; Savings evaluation based on baseline power value; Utilization of workstations evaluation (% of shift time); greenBOX power supply and temperature monitoring; VFD monitoring (communication, inputs, outputs). |